7501 Field-Mounted HART Temperature Transmitter
Brand: PR Electronics- RTD, TC, Ohm, and bipolar mV input and analog output
 - High definition local operator interface (LOI) with 3 optical buttons
 - Selectable red or white backlight
 - Ex d explosion proof / flameproof in aluminum or 316 stainless steel version
 - HART 7 functionality with HART 5 compatibility
 
High Defintion Display
- 0, 90, 180, & 270 degree position adjustments.
 - Monitoring, programming and diagnostics view.
 - Extensive diagnostics with flashing red or white backlight
 - Supports 7 languages.
 
Local Operator Interface (LOI)
- 3 optical buttons; up, down and enter.
 - Dynamically adaptive to wear or accumulation of dirt.
 - Immune to interference from ambient light sources.
 - Useable with or without gloves.
 
Configuration
- From the LOI through PR guided menu.
 - PReset and HART modem.
 - HHC, DCS or AMS via HART.
 
Mounting / Installation
- For installation in zone 0, 1, 2 and zone 20, 21, 22 and in Class 1, Division 1 and 2 applications.
 - Hardware assessed for use in SIL applications.
 - Mounting on 1.5”–2” pipe bracket or on wall / bulkhead.
 
Application
- Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
 - HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
 - Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
 - Amplification of bipolar mV signals to standard 4...20 mA current signals.
 - Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.
 
Technical Characteristics
- NAMUR NE43 and NE89.
 - HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
 
- 0, 90, 180, & 270 degree position adjustments.
 - Monitoring, programming and diagnostics view.
 - Extensive diagnostics with flashing red or white backlight
 - Supports 7 languages.
 - NAMUR NE43 and NE89.
 - HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
 
Specifications
Brand
Accuracy
- ± 0.05%
 
Approvals & Certifications
- 2014/30/EU
 - ATEX 2014/34/EU DEKRA 15-ATEX-0058 X
 - CSA 70024231
 - EAC Ex TR-CU 012 / 2011 RU C-DK.GB08V.01316
 - EAC TR CU 020/2011 EU RO Mutual Recognition Typical Approval
 - FM 3055380
 - IECEx DEK 15.0039 X
 - INMETRO DEKRA 15.0014 X
 - NEPSI GYJ15.1336X, GYJ.1337X & GYJ15.1338X
 
Calibration
- 20° to 28° C (68° to 82° F)
 
Enclosure, Body Material
- Low Copper Aluminum
 
Environmental Protection
- IP54
 - IP66
 - IP68
 - Typical 4X
 
Humidity
- 0 to 100% Relative Humidity (Condensing)
 
O-Ring Material
- FKM Rubber -20° C to 85° C (-4° F to 185° F)
 - Silicone Rubber -40° C to 85° C (-40° F to 185° F)
 
Output
- 4-20 mA Signal Range
 
Response Time
- 1 to 60 seconds Programmable
 
RTD Type
- Ni100
 - Ni1000
 - Ni120
 - Ni50
 - Pt100
 - Pt1000
 - Pt200
 - Pt50
 - Pt500
 
Storage Temperature
- -40° to 85° C (-40° to 185° F)
 
Supply Voltage
- 10 (12 with Backlight) to 30 Vdc - Intrinsically Safe
 - 10 (12 with Backlight) to 35 Vdc - Other
 
Temperature Range
- -20° to 85° C (-4° to 185° F) with FKM O-Ring
 - -40 to 85° C (-40 to 185° F) with Silicone O-Ring
 
Vibration
- ± 1.6 mm
 - ± 4 G
 
Documentation
Data Sheets
Certificates
- ATEX Certificate pdf 2.1 MB
 - CSA Certificate pdf 100 KB
 - DNV Marine Certificate pdf 194 KB
 - EAC Declaration pdf 355 KB
 - EAC Ex Certificate pdf 4.6 MB
 - FM Certificate pdf 533 KB
 - HART Certificate pdf 67 KB
 - IECEx Certificate pdf 186 KB
 - INMETRO Certificate pdf 2.4 MB
 - Metrology Pattern Approval (MPA), Russia pdf 8.0 MB
 - NEPSI Certificate pdf 1.6 MB
 - SIL Certificate pdf 100 KB